Please use this identifier to cite or link to this item: http://elar.urfu.ru/handle/10995/130992
Title: Evaluation of the Fast Synchrophasors Estimation Algorithm Based on Physical Signals
Authors: Senyuk, M.
Rajab, K.
Safaraliev, M.
Kamalov, F.
Issue Date: 2023
Publisher: MDPI
Citation: Senyuk, M, Rajab, K, Safaraliev, M & Kamalov, F 2023, 'Evaluation of the Fast Synchrophasors Estimation Algorithm Based on Physical Signals', Mathematics, Том. 11, № 2, 256. https://doi.org/10.3390/math11020256
Senyuk, M., Rajab, K., Safaraliev, M., & Kamalov, F. (2023). Evaluation of the Fast Synchrophasors Estimation Algorithm Based on Physical Signals. Mathematics, 11(2), [256]. https://doi.org/10.3390/math11020256
Abstract: The goal of this study is to evaluate the performance of the fast algorithm for synchrophasor estimation proposed on the basis of a physical system. The test system is represented by a physical model of a power system with four synchronous generators (15 and 5 kVA). Three synchronous machines represent steam turbine generators, while the fourth machine represents a hydro generator. The proposed method of accuracy assessment is based on comparison of the original and the recovered signals, using values of amplitude and phase angle. The experiments conducted in the study include three-phase faults, two-phase faults and single-phase faults at various buses of the test model. Functional dependencies of initial signal standard deviation from the recovered signal are obtained, as well as those for sampling rate and window width. Based on the results, the following requirements for measurement system and window width are formulated: sampling rate of analog-to-digital converter should be 10 kHz; and window width should start from 5 ms. In addition, the fast algorithm of synchrophasor estimation was tested on event recorder signals. The sampling rate of these signals was 2 kHz. Acceptable window width for event recorder signals is 8 ms. The algorithm was implemented using programming language Python 3 for the testing purposes. The proposed fast algorithm of synchrophasor estimation can be applied in methods for emergency control and equipment state monitoring with short time response. © 2023 by the authors.
Keywords: DIGITAL SIGNAL PROCESSING
PHASOR MEASUREMENT UNIT
POWER SYSTEM MODELING
SIGNAL ANALYSIS
URI: http://elar.urfu.ru/handle/10995/130992
Access: info:eu-repo/semantics/openAccess
cc-by
License text: https://creativecommons.org/licenses/by/4.0/
SCOPUS ID: 85146761778
WOS ID: 000927256900001
PURE ID: 33637153
ISSN: 2227-7390
DOI: 10.3390/math11020256
metadata.dc.description.sponsorship: National Science Foundation, NSF; Virginia Polytechnic Institute and State University, VT; Government of South Australia
Phasor measurement units (PMU) are important in control and modelling of modern power systems. Creation of the PMU had become possible due to launch of the global positioning system (GPS), increased computational capabilities, and development of digital processing algorithms, namely those for current and voltage []. The first prototype was built and tested at the Virginia Polytechnic Institute and State University in 1980s [], with support from the US government and the National Science Foundation. Synchrophasors estimation was carried out using the discrete Fourier transform (DFT).
Appears in Collections:Научные публикации ученых УрФУ, проиндексированные в SCOPUS и WoS CC