Citation: Kovalenko P. Y. Estimation of synchronous generator participation in low-frequency oscillations damping based on synchronized phasor measurements / P. Y. Kovalenko, Y. P. Zakharov, A. S. Berdin // WIT Transactions on Ecology and the Environment. — 2014. — Vol. 190 VOLUME 1. — P. 319-325.
Abstract: Large-scale centralized power systems interconnected by weak tie-lines is a typical feature of the state-of-the-industry power engineering. Another trend is distributed generation units integration with the resulting decrease of power system inertia constant and increasing sensitivity to small disturbances. In particular, in the case of significant power imbalance, periodic low-frequency oscillations of power system performance parameters may arise. Low frequency oscillations in power systems are inherently non-linear and non-stationary processes representing a superposition of numerous rotating masses movement components having mutual influence in a power region or power center. These situations imply the crucial role of monitoring each generator damping capability which is determined by the adjustment of the system regulators in use. To estimate the synchronous generator capability to maintain synchronous operation under deviating frequency and load angle conditions synchronizing torque and corresponding synchronizing power are proposed to be used. The possibility to determine the synchronous machine synchronizing power is subject to the presence of the load angle variation data with the techniques for defining load angle without direct measurement using a system of assumptions have been analyzed. Numerous simulations have shown that the effect of assumptions can be evaluated as acceptable. The main focus of the paper is the analysis of synchronizing power corresponding to the actual generator involved in the oscillations which had arisen after a disturbance in the Unified Energy System of Russia. The supposed cause of the oscillations is improper automatic excitation controller operation. © 2014 WIT Press.
Keywords: GENERATOR LOAD ANGLE
LOW-FREQUENCY OSCILLATIONS
PHASOR MEASUREMENTS
SYNCHRONIZING POWER
SYNCHRONOUS GENERATOR
DAMPING
ELECTRONIC EQUIPMENT
MEASUREMENT METHOD
OSCILLATION
SIGNAL
URI: http://elar.urfu.ru/handle/10995/75747
Access: info:eu-repo/semantics/openAccess
Conference name: 1st International Conference on Energy Production and Management in the 21st Century: The Quest for Sustainable Energy
Conference date: 23 April 2014 through 25 April 2014
SCOPUS ID: 84897908253
PURE ID: 379195
ISSN: 1743-3541
DOI: 10.2495/EQ140311
Sponsorship: International Journal of Safety and Security Engineering;International Journal of Sustainable Development and Planning;WIT Transactions on Ecology and the Environment
Appears in Collections:Научные публикации ученых УрФУ, проиндексированные в SCOPUS и WoS CC

Files in This Item:
File Description SizeFormat 
10.2495-eq140311.pdf655,86 kBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.